Installation and Setup Installing a PS6500 Array
2–15
Environmental Requirements
You must meet these environmental requirements for a PS6500 array:
• Only operate an enclosure from a power source with a voltage range of 100 to
240 VAC.
• Make sure your power source has sufficient electrical overload protection.
• In North America, connect the enclosure to a source of power with over-
current protection provided by a double pole 20A or less (LISTED circuit
breaker to UL489). In Europe, the over-current protection must be provided
by 20A or less (IEC circuit breakers).
• Make sure there is sufficient space for air flow in front of and behind the array
and make sure that the location is properly vented.
• Review the technical specifications inTable 2-6 to make sure your
environment supports its requirements.
Table 2-6: PS6500 Technical Specifications
Component Requirement
Weight without disk drives 77 pounds (35kg)
Weight with disk drives 177 pounds (80kg)
Operating temperature 41 to 95 degrees F / 5 to 35 degrees C
Storage temperature 34 to 140 degrees F / 1 to 60 degrees C
Operating altitude 0 to 10,000 feet (0 to 3048 meters)
Operational relative humidity 20 percent to 80 percent non-condensing
Storage relative humidity 5 percent to 80 percent non-condensing
Thermal output (fully-loaded array) 3400 BTU/hour
Operational shock 5G peak 1/2 sin, for 10ms
Operational vibration Random 0.21grms 5 - 500 Hz
Input voltage 100 to 240 VAC (auto-sensing)
Input frequency 50 - 60Hz
System input power 1400 VA (maximum)
Each power supply 440 watts DC output
Maximum input power: 0.7 KVA
Input current: 7 – 3.5A
Comments to this Manuals