Dell PowerEdge C8000 User Manual Page 266

  • Download
  • Add to my manuals
  • Print
  • Page
    / 294
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 265
266 Troubleshooting
Fresh air
mode
Upper
non-recoverable
52 °C
(125.6 °F)
Extremely high Fan controller (FC)
firmware shuts down the
system.
NOTE: The firmware reads
inlet temperature every 5 secs.
If the inlet temperature reaches
non-recoverable threshold, the
firmware will start to check the
power status for each sled and
initiate the sled for graceful
shutdown (pull-low 4 seconds).
Upper critical 50 °C
(122 °F)
High Chassis status indicator
lights amber.
Upper
non-critical
48 °C
(118.4
°F)
Warning Temperature events are
recorded in the SEL.
Table 5-6. Enclosure Air Inlet Temperature Threshold Settings
(continued)
Enclosure
Inlet
Condition
Threshold
Setting
Ambient
Temp
Threshold Level Action
Page view 265