Dell UPS 1920R User Manual Page 60

  • Download
  • Add to my manuals
  • Print
  • Page
    / 86
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 59
60
|
MIB-Objekte
Tabelle 11. IETF USV MIB-Objekte (Fortsetzung)
Bezeichnung der Variablen und relativer XML-Objektpfad VariableneinheitVariablentypOID
upsBypassNumLines
No Relative XML Object Path
1.5.2 Ganze Zahl
upsBypassVoltage
UPS.PowerConverter.Input[2].Voltage
1.5.3.1.2 Ganze Zahl V
upsBypassCurrent
UPS.PowerConverter.Input[2].Current
1.5.3.1.3 Ganze Zahl 0,1 A
upsBypassPower 1.5.3.1.4 Ganze Zahl W
upsAlarmsPresent
No Relative XML Object Path
1.6.1 Maßstab
upsAlarmTable
No Relative XML Object Path
upsAlarmBatteryBad
UPS.PowerSummary.PresentStatus.NeedReplacement
1.6.3.1
upsAlarmOnBattery
UPS.PowerSummary.PresentStatus.Discharging
1.6.3.2
upsAlarmLowBattery
UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit
1.6.3.3
upsAlarmDepletedBattery
Relative XML Object Path not implementated
1.6.3.4
upsAlarmTempBad
UPS.PowerSummary.PresentStatus.OverTemperature
1.6.3.5
upsAlarmInputBad
UPS.PowerConverter.Input[1].PresentStatus.VoltageOutOfRange
1.6.3.6
upsAlarmOutputBad
Relative XML Object Path not implementated
1.6.3.7
upsAlarmOutputOverload
UPS.PowerSummary.PresentStatus.Overload
1.6.3.8
upsAlarmOnBypass
UPS.PowerConverter.Input[2].PresentStatus.Used
1.6.3.9
upsAlarmBypassBad
UPS.PowerConverter.Input[2].PresentStatus.Good
1.6.3.10
upsAlarmOutputOffAsRequested
Relative XML Object Path not implementated
1.6.3.11
upsAlarmUpsOffAsRequested
Relative XML Object Path not implementated
1.6.3.12
Page view 59
1 ... 59 60 61 ... 86

Comments to this Manuals

No comments