Dell Technical Information Note (TIN UPS002) Authors Stephen Tavitas, Product Marketing Manager, Enterprise Product Group, Data Center Infras
Dell UPS Management Software: Common Software Installation Scenarios 10 Figure 5: ULNM edit modules settings Secondary server ULNM configuration: To
Dell UPS Management Software: Common Software Installation Scenarios 11 To set the power source: Click “Shutdown” menu “Edit Power Source” Select
Dell UPS Management Software: Common Software Installation Scenarios 12 Configuring multiple ULNM agents simultaneously For large installations where
Dell UPS Management Software: Common Software Installation Scenarios 13 Scenario 2: Single UPS, multiple servers, Ethernet connectivity using the NMC
Dell UPS Management Software: Common Software Installation Scenarios 14 Scenario 2: Installation notes Ensure the Dell UPS Network Management Card ha
Dell UPS Management Software: Common Software Installation Scenarios 15 Figure 14: ULNM edit shutdown configuration Scenario 2: Mass configuration o
Dell UPS Management Software: Common Software Installation Scenarios 16 Figure 16: MUMC auto discovery node list To perform a mass configuration o
Dell UPS Management Software: Common Software Installation Scenarios 17 To configure the Dell UPS: Click on the Dell UPS node in the “Node Settings”
Dell UPS Management Software: Common Software Installation Scenarios 18 Figure 19: Connectivity diagram for redundant Dell UPS with LAN connection t
Dell UPS Management Software: Common Software Installation Scenarios 19 Enable Redundant UPS Support in ULNM: To turn on the support for redundant U
Dell UPS Management Software: Common Software Installation Scenarios ii Contents Scope of this document ...
Dell UPS Management Software: Common Software Installation Scenarios 20 Figure 24: Creating the Composite (Redundant) UPS Device in ULNM Create a na
Dell UPS Management Software: Common Software Installation Scenarios 21 Figure 27: Power source composite redundant device APPENDIX I Firewall confi
Dell UPS Management Software: Common Software Installation Scenarios 22 APPENDIX 2 Shutdown settings To configure shutdown settings: Specify how yo
Dell UPS Management Software: Common Software Installation Scenarios 23 F. Load Segment: Only use this variable if you are using Load Segments to pre
Dell UPS Management Software: Common Software Installation Scenarios 24 Figure 30: Shutdown Sequence
Dell UPS Management Software: Common Software Installation Scenarios iii Figure 19: Connectivity diagram for redundant Dell UPS with LAN connection t
Dell UPS Management Software: Common Software Installation Scenarios 4 Scope of this document This document provides reference information when insta
Dell UPS Management Software: Common Software Installation Scenarios 5 Assumptions This document assumes that your deployment meets the following spe
Dell UPS Management Software: Common Software Installation Scenarios 6 Figure 2: Dell’s UPS Local Node Manager (ULNM) The Dell Multi-UPS Management
Dell UPS Management Software: Common Software Installation Scenarios 7 Figure 3: Dell’s Multi-UPS Management Console (MUMC) The Dell Multi-UPS Manag
Dell UPS Management Software: Common Software Installation Scenarios 8 In an environment with multiple host servers, the centralized MUMC console ena
Dell UPS Management Software: Common Software Installation Scenarios 9 Figure 4: Connectivity for Dell UPS with USB or RS232 connection to four Dell