Event Descriptions
|
Number RemarksType of MessageEvent Description
40 Service Battery Alarm and disables battery
charging (ABM in Charger Off
mode)
41 Utility Not Present Alarm and transfers to battery if
supporting the load; otherwise,
powers down
Utility level has fallen below the
Utility Not Present threshold
(typically < 25 to 50V).
42 Bypass Not Available Alarm and inhibits bypass
transfer
Applies to 5600W and
double‐conversion UPS models
only.
43 Input AC Overvoltage Alarm and transfers to battery if
supporting the load; otherwise,
turns off converters
44 Input AC Undervoltage Alarm and transfers to battery if
supporting the load or powers
down if not
45 Input Under/Over Frequency Alarm and transfers to battery if
supporting the load
46 Site Wiring Problem Alarm only
47 Remote Emergency Power Off Alarm and de‐energizes load and
enters standby mode
48 Overload L2 Alarm and then transfers to
bypass in 2 minutes
49 Overload L3 Alarm and then transfers to
bypass in 30 seconds
50 Battery DC Overvoltage Alarm only
51 Charger Failure Alarm only
52 Inverter AC Overvoltage Alarm and then transfers to
bypass if supporting the load or
if converters are off
Applies to double‐conversion
UPS models only.
53 Inverter AC Undervoltage Alarm and transfers to bypass if
supporting the load or if
converters are off
Applies to double‐conversion
UPS models only.
54 Rectifier Input Overcurrent Alarm and transfers to battery if
supporting the load or if
converters are off
Applies to double‐conversion
UPS models only.
55 Inverter Output Overcurrent Alarm and transfers to bypass if
supporting the load or if
converters are off
Applies to double‐conversion
UPS models only.