Installation on a VMware ESXi Server
|
4 Enter the shutdown commands (see Figure 124).
Example:
shutsys ip 172.18.127.47 e true
shutbackup ip 172.18.127.47 e true m 1:00
shutfile e true f /opt/ups/shutdownESXi.sh m 2
listshut –ip 172.18.127.47
NOTE:
See ”Dell CUI Commands” on page 133 for a description of all Dell CUI commands.
NOTE: Each guest operating system requires a minimum of 30 seconds to run the command file before
shutdown. The -m 1 option in the shutfile command in the example below sets one minute as the total time
allowed to run the command file before shutdown, which allows sufficient time for two guest operating systems.
Example: shutfile -e true -f /opt/ups/shutdownESXi.sh -m 1