Installation on a VMware ESXi Server
|
NOTE: All hardware elements must have an operational network configuration that allows them to
communicate freely with each other. The Dell UPS Management Software uses TCP and UDP for
communication with UPS.
4 Confirm that the following UDP ports are enabled on the VIMA/vMA firewall: 161, 162, and 3369
Example commands:
sudo iptables I INPUT p udp dport 161 j ACCEPT
sudo iptables I OUTPUT p udp dport 161 j ACCEPT
5 Confirm that the following TCP port is enabled on the VIMA/vMA firewall: 2099
Dell UPS Management Software Installation
To install the software:
1 Start the vMA 4.0 guest operating system.
2 Download the software from the Dell Web site (support.dell.com) or from the CD (F618R A04 or
higher) provided with the UPS.
3 Upload the software from Windows to vMA 4.0 using WinSCP tools.
4 Copy the Linux and InstallerData files from the CD to vMA.
5 Enter the following commands to access the Linux and InstallerData files:
sudo chmod R 777 Linux
sudo chmod R 777 InstallerData
6 Enter the Linux path and then enter the following command to install the software:
cd Linux
sudo ./setup_console.bin
7 Edit the document “VMwareESXHosts” on the installation path.
Add all ESXi server host IP addresses, separated by spaces. Add the IP address of the ESXi server
on which VIMA/vMA is installed as the last entry.
Example: 172.18.127.13 172.18.127.12 172.18.127.11
NOTE:
To configure each server, see “vMA Configuration” on page 120.
8 Start the Agent. From the installation path, enter the command:
sudo ./agent start